School Kitchen Gas-Extraction Interlock Procedure

To provide a procedure for schools with kitchen gas equipment and an extract system intended to remove gas fumes or leaks during cooking, covering specification, verification, testing and management of the interlock between the kitchen extraction system and the gas supply.

SOP Template
CalmComplianceSOP Template

School Kitchen Gas-Extraction Interlock Procedure

Version
v1
Updated
1 October 2026

Fields in brackets are completed when you adapt this template.

Use this procedure where the school has kitchen gas equipment and an extract system intended to remove gas fumes or leaks during cooking. Apply it to the actual kitchen installation and controls at [site name].

Purpose and operating principle

Where kitchen extraction is used to control gas fumes or leaks, the extract system should be linked to the gas supply so that gas cannot flow while the extract system is not working.

1. Confirm applicability

Before applying this procedure, confirm whether [kitchen location] has gas equipment used during cooking and an extract system intended to remove gas fumes or leaks. If either element is absent, record the reason this procedure does not apply to the installation.

2. Specify the interlock

Define the relevant kitchen gas supply, gas equipment and extract system in the installation specification. Specify that the extract system is linked to the gas supply so that gas cannot flow while the relevant extract system is not working.

Record the installation-specific arrangement, including [gas supply identifier], [extract system identifier] and [interlock control description].

3. Verify the installation

Verify the kitchen equipment and gas-system specification against the actual installation and controls. Confirm that the specified extract system is the system linked to the relevant gas supply.

Record the verification by reference to [kitchen equipment and gas system specification] and identify any discrepancy for corrective action.

4. Test the interlock

Test the interlock using the actual kitchen installation and controls. Verify that gas cannot flow while the relevant extract system is not working.

Record the test date, the installation tested, the result and the person or organisation carrying out the test in [interlock test record]. Do not treat the interlock as verified where the required result has not been demonstrated or the test result is not available.

5. Manage defects and corrective action

Record any defect, failure or discrepancy affecting the link between the extract system and the gas supply in [defect and corrective action record]. Describe the affected equipment or control, the required corrective action and the person or organisation responsible for addressing it.

Retain the relevant maintenance certificate or other maintenance record for the installation in [maintenance record location].

6. Review the arrangement

Review this procedure when the kitchen equipment, gas system, extract system or interlock controls change, and when a defect or corrective action indicates that the documented arrangement no longer reflects the actual installation.

The person responsible for the installation at [responsible role] should ensure that the specification, interlock test records, maintenance certificates and defect or corrective-action records remain identifiable for the applicable kitchen installation.

Sources

  1. Good estate management for schools - Health and safety - Guidance - GOV.UK Department for Education
CalmCompliance · v1Template for adaptation

Template details

Type
SOP Template
Version
v1
Updated
1 October 2026
Sections
21 sections
  • Good estate management for schools - Health and safety - Guidance - GOV.UK

Get this template

Free, editable Word document. We’ll email you a download link. No Calm account needed.

Edit in Word or Google Docs.

We record your email and the template you request. Read our privacy policy.

School Kitchen Gas-Extraction Interlock Procedure template - CalmCompliance